Match the actual products
Select the raceway schedule, insulation family, conductor size, and quantity. For a listed cable, use the manufacturer's actual outside diameter.
Free field tool · no sign-in
Check a mixed run, find the maximum wire count, or choose the minimum conduit size—with the math shown.
Within fill limit. 39.4% used; 40 percent allowed. Minimum EMT 1/2 inches.
Area-scaled schematic — not a physical pulling layout
Fill check only. Grounds occupy fill. Current-carrying count, ampacity adjustment, environment, bends, and local amendments require a separate review.
Chapter 9 quick reference
The tool chooses the governing column automatically and keeps the published allowable area separate from total raceway area.
Interactive reference
Same-size conductor capacities are generated by the same engine as the calculator. Select any number to load that exact configuration above.
| Trade size | #14AWG | #12AWG | #10AWG | #8AWG | #6AWG | #4AWG | #3AWG | #2AWG | #1AWG | #1/0AWG | #2/0AWG | #3/0AWG | #4/0AWG |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1/2"(16) | |||||||||||||
| 3/4"(21) | |||||||||||||
| 1"(27) | |||||||||||||
| 1-1/4"(35) | |||||||||||||
| 1-1/2"(41) | |||||||||||||
| 2"(53) | |||||||||||||
| 2-1/2"(63) | |||||||||||||
| 3"(78) | |||||||||||||
| 3-1/2"(91) | |||||||||||||
| 4"(103) |
*Count-specific limits still govern. A single conductor uses the 53% column, two use 31%, and three or more use 40%. Eligible nipples use 60%.
Same-size capacities include the Chapter 9 Note 7 ≥0.8 rounding rule. Mixed physical areas must be calculated above and are never rounded this way.
Transparent calculation
The calculator adds the published physical area of every conductor or cable, then compares that total with the selected raceway's published allowable area. It never treats fill as ampacity approval.
2026 reference basis: NFPA 70 Chapter 9 Table 1 and Notes 4, 7, and 9; Table 4 raceway areas; and Table 5 round concentric-lay THHN/XHHW areas. Compact conductors and Table 5A values are not assumed—use the listed manufacturer area or actual cable OD.
Add occupied areaQuantity × physical area for each conductor group.
Select the limit53% for one, 31% for two, 40% for three or more, or 60% for an eligible nipple.
Evaluate and sizeCompare areas, apply same-size Note 7 only when eligible, then scan upward for the minimum trade size.
Field workflow
Use the tool as a fast area check, then verify the conditions the fill calculation cannot know.
Select the raceway schedule, insulation family, conductor size, and quantity. For a listed cable, use the manufacturer's actual outside diameter.
The minimum size is the calculated threshold. The field-friendly option is one trade size larger when available—often a better pull.
Count grounds for fill, then separately check current-carrying conductors, adjustment factors, temperature, bends, pull tension, and local amendments.
Worked examples
Each example opens in the same calculator—no dead-end article or new page.
Common field questions
These answers explain the scope behind the instant result. The authority having jurisdiction makes the final determination.
Run your configuration ↑Yes. Equipment grounding and bonding conductors occupy physical space, so include them in the fill calculation. Whether a conductor counts as current-carrying for ampacity adjustment is a separate question.
The governing percentage depends on the number of conductors or cables in the raceway: 53% for one, 31% for two, and 40% for three or more. The calculator switches columns automatically.
Only for a raceway nipple no longer than 24 inches installed between boxes, cabinets, or similar enclosures. Connector length is not part of the 24-inch raceway length. Confirm that the actual installation qualifies.
Add the physical area of every conductor group, then compare the sum with the raceway's allowable area. Do not add capacities from a same-size chart, and do not use Note 7 rounding on a mixed physical-area set.
No. Raceway fill and ampacity adjustment are separate checks. Neutral behavior, spares, nonlinear loads, ambient temperature, terminal ratings, and a qualifying nipple can all change the ampacity review.
Choose Custom cable OD and enter the listed manufacturer's actual outside diameter. For an elliptical cable, use its major diameter as the diameter of a circle. Cable constructions vary too much to infer safely from a category name.
Chapter 9 Note 7 allows the next whole same-size count when the unused decimal capacity is 0.8 or greater. The calculator labels this exception; it never applies that rounding to mixed physical areas.
The minimum is the area-based threshold. A larger raceway can reduce pulling difficulty and leave useful margin, especially with long runs, bends, large conductors, or a possible three-conductor jam condition.